Keeping a CRAY-1 cool and powered

Freon cooling loop · 400 Hz power · schematic

The heat path

Every module carries a heavy copper plate between its two circuit boards. The plate is wedged along both 8-inch edges against the cold bars that line the column walls. Each cold bar is cast aluminium with a stainless steel tube inside, through which Refrigerant-22 (Freon) carries the heat away to the condensing units, where it is handed over to water. The power supplies sit on refrigerant-cooled heat sinks as well.

The power distribution unit monitors temperatures on the chassis and has automatic warning and shutdown circuits. Switch the cooling off: the module temperature climbs, the warning comes on, and the model switches the power off.

Documented figures (CRAY-1 S Series)

Input power, maximum memory≈ 118 kW
Supply400 Hz, 3-phase, from motor-generators
DC power supplies36 (12 columns), 24 (8 columns)
Supply voltages per module−5.2 V and −2.0 V
RefrigerantR-22, heat exchange to water
Maximum IC case temperature (design)54 °C

Temperatures during operation, the warning and shutdown thresholds and the warm-up and cool-down curves are illustrative, not measured values. The schematic is not to scale. Sources: CRAY-1 S Series Hardware Reference Manual HR-0808; R. M. Russell, The CRAY-1 Computer System (1978).