Every module carries a heavy copper plate between its two circuit boards. The plate is wedged along both 8-inch edges against the cold bars that line the column walls. Each cold bar is cast aluminium with a stainless steel tube inside, through which Refrigerant-22 (Freon) carries the heat away to the condensing units, where it is handed over to water. The power supplies sit on refrigerant-cooled heat sinks as well.
The power distribution unit monitors temperatures on the chassis and has automatic warning and shutdown circuits. Switch the cooling off: the module temperature climbs, the warning comes on, and the model switches the power off.
| Input power, maximum memory | ≈ 118 kW |
| Supply | 400 Hz, 3-phase, from motor-generators |
| DC power supplies | 36 (12 columns), 24 (8 columns) |
| Supply voltages per module | −5.2 V and −2.0 V |
| Refrigerant | R-22, heat exchange to water |
| Maximum IC case temperature (design) | 54 °C |
Temperatures during operation, the warning and shutdown thresholds and the warm-up and cool-down curves are illustrative, not measured values. The schematic is not to scale. Sources: CRAY-1 S Series Hardware Reference Manual HR-0808; R. M. Russell, The CRAY-1 Computer System (1978).